The Schneider Electric Acti9 iCV40N A9DE7610 is a residual current circuit breaker with overcurrent protection, also known as a RCBO, which combines in a single device thermal-magnetic protection against overloads and short circuits with residual current protection against earth leakage currents. It features a 1P+N configuration, rated current of 10 A, C curve, residual current sensitivity of 300 mA and AC type, offering a compact solution for distribution electrical panels.
The A9DE7610 reference belongs to Schneider Electric's professional Acti9 iCV40N range. It has one protected pole and neutral, operates at 230 V AC and 50/60 Hz, and offers a rated breaking capacity of 6 kA according to EN/IEC 61009. Its 36 mm format allows thermal-magnetic and residual current protection to be integrated while occupying only two conventional modules in the panel.
Unlike a conventional residual current device, the Acti9 iCV40N A9DE7610 also incorporates overcurrent protection. In this way, a single device protects the circuit against different types of electrical fault.
This combination reduces the number of devices required in the panel and facilitates individual protection of lines and circuits.
The Schneider Electric A9DE7610 has a 1P+N configuration. The phase pole incorporates thermal-magnetic protection, while the neutral is disconnected together with the phase.
The thermal-magnetic protection uses a C tripping curve, suitable for many distribution circuits with moderate inrush currents.
The magnetic tripping threshold of a C curve is in the range of 5 to 10 times the rated current. In this 10 A model, magnetic operation is designed to respond quickly to high short-circuit currents.
The A9DE7610 incorporates residual current protection with a rated sensitivity of 300 mA and type AC class. This class is designed to detect sinusoidal alternating residual currents.
A 300 mA sensitivity is mainly used as protection against insulation faults and fire risk and should not be confused with the 30 mA devices commonly used as additional protection against electric shock.
The Acti9 iCV40N A9DE7610 has a rated breaking capacity Icn of 6 kA at 230 V AC according to EN/IEC 61009.
The iCV40N family is developed for applications that require a higher breaking capacity than the standard iCV40 variant. Schneider Electric specifies for the iCV40N range a capacity of 10 kA according to IEC/EN 60947-2 under the conditions established by that standard.
This residual current-magnetic circuit breaker is designed for single-phase low-voltage installations.
The residual current protection is instantaneous, with no intentional time delay. When the device detects a differential current that reaches the specified operating level, it disconnects the protected circuit.
This function is combined with the integrated thermal and magnetic protections to provide multiple protection from a single modular device.
The Acti9 iCV40 range includes local indication to make it easier to identify the device status and tripping events. This helps distinguish a protection operation and simplifies diagnosis in panels with multiple circuits.
The Acti9 design also includes contact position indication and features aimed at facilitating maintenance and installation checks.
Schneider Electric specifies suitability for isolation or disconnection according to EN/IEC 61009-2-1. This allows the device to be used to isolate the circuit within the conditions provided by the manufacturer and applicable regulations.
One of the main advantages of the iCV40N is the integration of the two protection functions in a compact format. The A9DE7610 reference has a width of 36 mm, equivalent to four 9 mm pitches or two conventional 18 mm modules.
The Schneider Electric A9DE7610 is designed for clip-on DIN rail mounting, making it easy to integrate into modular distribution panels.
The terminals can be used from the top or bottom and allow flexible installation inside the panel.
The RCBO includes tunnel terminals suitable for rigid and flexible conductors.
The Acti9 iCV40N is designed to offer a long service life in professional electrical panels.
The device has an IP20 protection rating according to IEC 60529. Properly installed inside a suitable modular enclosure, it can achieve a higher front protection rating depending on the panel configuration.
The Schneider Electric Acti9 iCV40N A9DE7610 is developed in accordance with the standards applicable to residual current circuit breakers with overcurrent protection, including EN/IEC 61009-2-1.
Its integrated design makes it possible to have in a single device the functions that would otherwise require a separate MCB and residual current protection.
The Schneider Electric Acti9 iCV40N A9DE7610 is a compact solution for protecting single-phase circuits with a single device. Its 10 A, C curve, 300 mA type AC residual current sensitivity and 6 kA breaking capacity make it possible to combine protection against overloads, short circuits and leakage currents while occupying only 36 mm in the electrical panel.