The Schneider Electric Linergy LGY vertical profile LVS04505 is a high-current busbar distribution bar designed for building vertical busbars in PrismaSeT P electrical switchboards. It has a rated operational current of 1250 A, a length of 1,670 mm, and cross-sectional dimensions of 32.5 x 42.5 mm, providing a modular solution for power distribution within low-voltage switchboards.
This profile belongs to the Schneider Electric Linergy LGY system and is designed to be installed vertically in either rear or side position within compatible enclosure configurations. Its design with a single T-slot and free connection position makes it easy to connect busbar elements along the profile and provides flexibility during switchboard design and assembly.
The LVS04505 is intended to be part of the Linergy electrical distribution system inside PrismaSeT P switchboards. Its function is to carry and distribute high currents through the main busbar of the switchboard, allowing the necessary connections to be made to the different devices and circuits.
Its 1250 A rated current places it among the Linergy solutions designed for high-power distribution boards, where a busbar system capable of carrying significant currents in an orderly manner and in accordance with Schneider Electric tested configurations is required.
The profile has a nominal length of 1,670 mm, equivalent to 1.67 meters. This measurement is specifically designed for compatible vertical configurations in PrismaSeT P switchboards.
The profile length provides a wide vertical distribution area inside the enclosure, making it easier to connect different elements along the busbar according to the electrical design of the switchboard.
Schneider Electric specifies the LVS04505 for use with PrismaSeT P enclosures. It can be installed in cell configurations of:
Integration within the PrismaSeT system allows the profile to be combined with supports, connections, and other Linergy components intended to build a complete busbar assembly.
The profile is designed for vertical installation, and Schneider Electric provides two operating positions:
The selected position and the number of supports used directly affect the permissible short-time current rating of the assembly, so the tested and specified configurations by Schneider Electric must be respected.
The ability to withstand short-circuit currents for one second depends on the profile position and the number of supports used. Schneider Electric specifies the following Icw values for the LVS04505:
These values show the importance of using the correct number of supports and respecting the mounting arrangement established by the manufacturer. The final busbar configuration must be selected according to the short-circuit current expected in the installation.
In addition to its 1250 A rated operational current, Schneider Electric provides permissible current values at an ambient temperature of 35 °C depending on the enclosure protection rating:
These values reflect the influence of ventilation and enclosure sealing on busbar thermal dissipation. Final sizing must be carried out considering the actual switchboard conditions and Schneider Electric tables.
The profile has a rated insulation voltage Ui of 1000 V, suitable for low-voltage distribution systems installed within the limits defined by Schneider Electric.
It also has a rated impulse withstand voltage Uimp of 12 kV with pollution degree 3, providing insulation capability against transient overvoltages within the conditions established by the relevant standards.
The Linergy LGY profile has cross-sectional dimensions of 32.5 x 42.5 mm. Its specific geometry is part of the Linergy design and should not be confused with a conventional flat bar.
Schneider Electric uses an exclusive profile that combines electrical conductivity, mechanical strength, and multiple connection possibilities within tested busbar configurations.
The LVS04505 incorporates a single T-slot connection system. This geometry allows compatible Linergy system components to be fixed to the profile without relying on a single predetermined connection position.
Schneider Electric specifies a free connection position, providing flexibility to distribute connections along the busbar according to the switchboard architecture.
Schneider Electric's Linergy range brings together different solutions for distribution and connection inside electrical switchboards. The LVS04505 profile is part of the vertical busbar system and can be combined with the supports and accessories provided by the manufacturer to create a power distribution system adapted to the project.
Using components from the same system makes it easier to design switchboards following Schneider Electric verified configurations and helps maintain consistency between busbars, supports, connections, and enclosures.
The profile is specified in accordance with IEC 61439-1 and IEC 61439-2, relating to low-voltage switchgear assemblies and power distribution boards.
The final performance of the assembly depends on the complete switchboard configuration, including the number and position of supports, profile arrangement, connections, enclosure, temperature, and other elements covered by the verified design.
Schneider Electric indicates ASTA certification for this product. The tests and certifications associated with the system help support the declared performance within the specified mounting configurations.
The profile has a net weight of approximately 3.38 kg and a natural finish. It is supplied as one unit per set.
Due to its 1,670 mm length, care must be taken during transport, handling, and installation to avoid any deformation of the profile that could later affect the correct installation of the busbar or its connections.
This profile is especially suitable for building busbars in high-current low-voltage distribution boards, including:
The Schneider Electric LVS04505 provides a specific solution for building vertical busbars of up to 1250 A within the PrismaSeT P system. Its 1,670 mm length, rear or side mounting, T-slot with free connection position, and short-time withstand capability of up to 60 kA for 1 second depending on the configuration make it suitable for high-power electrical switchboards.
To ensure the performance indicated by Schneider Electric, the profile must be installed using compatible Linergy supports, connections, and accessories and respecting the position, number of supports, and configuration defined for the switchboard. Busbar sizing and assembly must be carried out by qualified professionals in accordance with the manufacturer's technical documentation and applicable standards.